General Checklist List the Essential Steps and precautions for Pre start and Starting up the Centrifugal Pumps
As
General Checklist List the Essential Steps and for Pre start and
Starting up the Centrifugal Pumps ⁉️
️
What’s the things you Should be attention physically⁉
✅ General centrifugal pump start
up procedure:-
Before pump start-up you must perform these tasks:-
1️⃣ Open the
suction valve , do priming by venting all the air inside the suction line by
opening any vent or even the PG vent till liquid coming out then close , now
you confirm no air inside the system to reduce the chances of pump getting
cavitation
2️⃣ Open any recirculation or cooling lines.
3️⃣ Fully close or
partially open the discharge valve, depending on system conditions.
4️⃣ Start
the driver.
5️⃣ Slowly open the discharge valve until the pump reaches the
desired flow.
6️⃣ Check the pressure gauge to ensure that the pump quickly
reaches the correct discharge pressure.
7️⃣ If the pump fail to reach the
correct pressure, perform these steps: a. Stop the driver. b. Prime the pump
again. c. Restart the driver.
8️⃣ Monitor the pump while it is operating. a.
Check the pump for bearing temperature, vibration, and noise. b. If the pumps
exceed normal levels, then shut down the pump immediately and correct the
problem.
9️⃣ Repeat steps 7 and 6 until the pump runs properly.
Comments